RL260-25W1-10R Surge protector

Description:DIN rail, combined Type 1 & 2/ClassⅠ& Ⅱwith MOV and CDGG technology for use in 230/400 Vac power supply system at boundaries from LPZ 0A -2.

Features:

1,MOV&CDGG Tech nology

2, Non-follow current

3, Combined disconnection device

4,High discharge capacity

5,Capable of protection terminal equipment

6,Visual and remote status indication

7,Multifunctional terminal for connecting conductors and busbars

Description

Part Number RL260-
25W1-10R
RL260-
25W1-10
Nominal Voltage( Un) 230/400Vac 230/400Vac
Max. continuous operating voltage (Uc) 260Vac 260Vac
Nominal discharge current (8/20 µs) (In) 25kA 25kA
Lightning impulse current (10/350 µs) (limp) 25kA 25kA
Specific energy(W/R) 156.25KJ/ohms 156.25KJ/
ohms
Charge 12.5As 12.5As
Follow current extinguishing capability (IfI) Infinite Infinite
Voltage protection level (Up) 1.5kv 1.5kv
Voltage protection level for 5kA (Up) 1.0kv 1.0kV
Response time (tA) ≤100ns ≤100ns
Short-circuit withstand capability(Iscw) 25kArms 25kArms
Temporary over voltage(TOV) (Ut) 440V/5s 440V/5s
Max. overcurrent protection ≤250A gL/gG ≤250A gL/
gG
TOV characteristic Withstand Withstand
Approval CE CE