RL260-100W1-01 Power Distribution System Surge Protector,SPD

Description:DIN rail, combined Type 1 & 2/ClassⅠ& Ⅱwith MOV and CDGG technology for use in 230/400 Vac power supply system at boundaries from LPZ 0A -2 and specially designed for installation between N and PE.

Features:

● CDGG Technology

● High discharge capacity

● Capable of protection terminal equipment

● Visual and remote status indication

● Multifunctional terminals for connecting conductors and busbars

Description

Part Number RL260-100W1-01
Nominal Voltage ( Un) 230/400Vac
Max. continuous operating voltage (Uc) 260Vac
Nominal discharge current (8/20 µs) (In) 100kA
Lightning impulse current (10/350 µs) (limp) 100kA
Specific energy(W/R) 2500KJ/ohms
Charge 50As
Follow current extinguishing capability (If i) 100Arms
Voltage protection level (Up) 1.8kv
Voltage protection level for 5kA (Up) 1.0kV
Response time (tA) ≤100ns
Short-circuit withstand capability(Iscw)
Temporary overvoltage (TOV) (Ut) 1455V/200ms
Max. overcurrent protection
TOV characteristic Withstand
Approval CE