RL260-25W1-31 Power Distribution System Surge Protector

Description:DIN rail, combined Type 1 & 2/ClassⅠ& Ⅱwith CDGG technology for use in TN-S、TT power supply network system at boundaries
from LPZ 0A-2.

Feature:

● CDGG Technology

● High discharge capacity

● Capable of protection terminal equipment

● Multifunctional terminals for connecting conductors and busbars

● DIN rail installation

Description

Part Number RL260-25W1-31
Nominal Voltage (Un) 230/400Vac
Max. continuous operating voltage (Uc) 260Vac(L-N),260Vac(N-PE)
Nominal discharge current (8/20 µs) (In) 25kA(L-N),100kA(N-PE)
Lightning impulse current (10/350 µs) (limp) 25kA(L-N),100kA(N-PE)
Specific energy(W/R) 156.25KJ/ohms(L-N),2500KJ/ohms(N-PE)
Charge 12.5As(l-N),50As(N-PE)
Follow current extinguishing capability (If i) 10kArms
Voltage protection level (Up) 2.0kV
Voltage protection level for 5kA (Up) 1.0kV
Response time (tA) ≤100ns
Short-circuit withstand capability(Iscw) 10kArms
Temporary overvoltage (TOV) (Ut) 440V/5s
Max. overcurrent protection ≤250A gL/gG
TOV characteristic Withstand